Caveat Lector: Although great care has been taken in the compilation of the information contained on this web site, the authors are not liable for the accuracy in terms of error or omission. The information on this web site is subject to change without notice and without obligation on the part of the authors. The authors shall not be liable for technical failures or for failures beyond their control. Some posts may contain authors' personal opinions and views and the authors do not represent any company, corporation or institution.

Monday, July 9, 2012

Tripping of Customer 69kV Line ( July 5, 2012 at 1934H )

Below is my root cause analysis (RCA) for the tripping of our 69kV Line. Since I could not speak for the Test and maintenance section-Relay Group, I presented the root cause using simple calculation and analysis. Please leave comments below for the improvement of this RCA.

Thursday, March 8, 2012

Root Cause Analysis: Oil Trace at Phase B of 115kV Current Transformer

I. BACKGROUND OF THE PROBLEM:


      February 28, 2011, 1705H- The Senior Engineer on-duty , observed the oil trace on the head of phase B of 115kV current transformer while doing his daily routine inspection.