Caveat Lector: Although great care has been taken in the compilation of the information contained on this web site, the authors are not liable for the accuracy in terms of error or omission. The information on this web site is subject to change without notice and without obligation on the part of the authors. The authors shall not be liable for technical failures or for failures beyond their control. Some posts may contain authors' personal opinions and views and the authors do not represent any company, corporation or institution.

Monday, November 2, 2015

ACCESS OF FAULT DATA: ABB SPAA 331C Overcurrent Relay

Below is the procedure in the access of fault indications of the ABB SPAA 331C Overcurrent Relay. Most substation engineers are limited in the access of relay indications and readings especially during faults or retrieval of data since there is a separate group that handles relay testing and setting.  I am not familiar with the latest relay tester already that is why I could not include relay setting and testing.



Note: No recorded fault current values
   Recorded information that can be retrieved:
    1-Maximum phase current value, 2-number of start I>;, 3-number of start I>>;, 4-duration of start
     I>;, 5-duration of start I>>;


1. On SPJC 3C3 and 1C8 module, press  “ STEP ” button for 1sec to scroll the real-time measured values (rightmost 3-digits on the display), indicated by a lit indicator (e.g. IL1, IL2, IL3, …).


2. Press  “STEP”  button for 0.5sec to go back each display sequence

3. To go to main display, just press the “STEP” button continually until  the display has no indication (black screen).

4. For SPCT 2C17 autorecloser, it has been disabled since all of the switches (SG1-SG8) are set to 0.


SPJC 3C3 (IL1, IL2, IL3)

SPJC 1C8 (Io component)



SPCT 2C17 (Autorecloser) -DISABLED




Reference: ABB SPAA 331C manual